UNITED STATES OF AMERICA
BEFORE THE

FEDERAL ENERGY REGULATORY COMMISSION

 

 

Petition of the North American Electric)Docket No.RD14-7-000

Reliability Corporation for Approval of)

Proposed Reliability Standard PER-005-2)

and Retirement of Reliability Standard)

PER-005-1)

 

JOINT MOTION TO INTERVENE AND COMMENTS OF CALIFORNIA

INDEPENDENT SYSTEM OPERATOR CORPORATION; ELECTRIC RELIABILITY
COUNCIL OF TEXAS, INC.; INDEPENDENT ELECTRICITY SYSTEM OPERATOR;
ISO NEW ENGLAND INC.; MIDCONTINENT INDEPENDENT SYSTEM OPERATOR,

INC.; NEW YORK INDEPENDENT SYSTEM OPERATOR, INC.; AND SOUTHWEST
POWER POOL, INC.

Pursuant to Rules 212 and 214 of the Rules of Practice and Procedure of the Federal

Energy Regulatory Commission (the “Commission”), 18 C.F.R. §§ 385.212 and 214 (2013),

California Independent System Operator Corporation, Electric Reliability Council of Texas, Inc., Independent Electricity System Operator, ISO New England Inc., Midcontinent Independent
System Operator, Inc., New York Independent System Operator, Inc., and Southwest Power
Pool, Inc. (the “ISO/RTO Commenters”) move to intervene in the above-captioned proceeding, and submit these supporting joint comments in response to the petition of the North American Electric Reliability Corporation (“NERC”), filed March 7, 2014, for the approval of Reliability Standard PER-005-2 - Operations Personnel Training (the “PER Standard”), and the retirement of Reliability Standard PER-005-1 (the “Petition”).

Reliability Standard PER-005-1 was intended to serve “the important reliability goal of
helping to ensure that System Operators performing Real-time, reliability-related tasks on the
[Bulk Electric System (“BES”)] are adequately trained to competently perform those tasks and


 

 

reliably operate the BES.”1  The purpose of the proposed revision (Reliability Standard PER005-2) is to “improve upon PER-005-1 by expanding the scope of the Reliability Standard to include training requirements” for additional types of personnel.2

I.COMMUNICATIONS

Correspondence and communications regarding this filing should be addressed to the

undersigned as follows:

Roger E. CollantonMatthew Morais*

General CounselDirector, Federal Policy

Anna A. McKenna*Electric Reliability Council of Texas, Inc.

Assistant General Counsel-Regulatory2705 West Lake Drive

California Independent System OperatorTaylor, Texas 76574

Corporationmmorais@ercot.com

250 Outcropping Way

Folsom, California 95630

amckenna@caiso.com

Jessica Savage*Raymond W. Hepper

Manager, Government and RegulatoryVice President, General Counsel and Corporate

AffairsSecretary

Independent Electricity System OperatorTheodore J. Paradise*

Station A, Box 4474Assistant General Counsel - Operations and

Toronto, Ontario  M5W 4E5Planning

jessica.savage@ieso.caMargoth R. Caley

Regulatory Counsel

ISO New England Inc.

One Sullivan Road

Holyoke, MA 01040-2841

tparadise@iso-ne.com

 

 

 

 

 

 

 

 

 

 

 

1 Petition at 2.

2 Petition at 3.

 

 

2


 

 

 

 

 

Stephen G. Kozey*Carl F. Patka*

Senior Vice-President, Legal andAssistant General Counsel

Compliance Services, General Counsel andChristopher Sharp

SecretaryCompliance Attorney

Midcontinent Independent SystemRaymond Stalter

Operator, Inc.Director, Regulatory Affairs

P.O. Box 4202New York Independent System Operator,

Carmel, Indiana 46082-4202Inc.

skozey@midwestiso.org10 Krey Blvd.

Rensselaer, New York 12144

cpatka@nyiso.com

Paul Suskie*

Executive Vice President, Regulatory Policy and General Counsel

Southwest Power Pool, Inc.

201 Worthen Drive

Little Rock, AR  72223

psuskie@spp.org

 

*/ = persons identified for service

II.MOTION TO INTERVENE

The ISO/RTO Commenters move to intervene in this proceeding, as the roles they perform with regard to the Bulk Electric System may be implicated by this Petition and the proposed Reliability Standard.

III. BACKGROUND AND COMMENTS

The ISO/RTO Commenters supports adoption of the PER Standard as drafted, for a number of reasons.

First, the scope of personnel subject to the training requirements reasonably identifies

 

individuals who may affect real-time system operations/reliability.  For the Reliability

Coordinator (“RC”), Balancing Authority (“BA”) and Transmission Operator (“TOP”) functions, the scope of personnel includes System Operators and Operations Support Personnel.3  For

 

 

3 See proposed Reliability Standard PER-005-2, Requirements R1 and R5.

 

 

3


 

 

 

 

 

Transmission Owners (“TOs”) and Generator Operators (“GOPs”), the scope of personnel

includes those whose duties include specific real-time operations-related tasks (as described in the proposed standard).4

Second, the scope of the training obligations under the PER Standard is also reasonable.
The standard requires each relevant entity to implement a systematic approach to training for
pertinent individuals.  In addition, the PER Standard explicitly states that each functional entity
must design and develop training materials according to its training program.5  Such training
relates to the real-time reliability tasks identified by the applicable functional entity.6  This
approach appropriately gives the functional entity the discretion to scope its training based on the
particular processes and procedures utilized by that entity in the administration of its real-time
operations-related functions.  It also allows the functional entity to establish procedures for
training different types of personnel (i.e., System Operators and Operations Support Personnel).
The functional entities are in the best position to understand their relationship to real-time
operations and reliability; consequently, they should have the discretion to develop the scope and
implementation procedures for this standard.

With respect to the RC, BA and TOP functional entities’ training obligations for System
Operators and Operations Support Personnel, the ISO/RTO Commenters support the different
scope of training for support personnel - i.e., they only need to be trained on how their jobs
impact the company-specific real-time reliability-related tasks.7  This distinction is appropriate
because support personnel do not actually perform real-time reliability-related tasks, and

 

 

4 See proposed Reliability Standard PER-005-2, Applicability Sections 4.1.4.1 and 4.1.5.1.

5 See proposed Reliability Standard PER-005-2, Requirements R1.2 and R2.2.

6 See proposed Reliability Standard PER-005-2, Requirements R1, R2, R5 and R6.

7 Compare Requirement R1 (for System Operators) with Requirement R5 (for Operations Support Personnel).

 

 

4


 

 

therefore do not require the same level/type of training as System Operators.  Indeed, the PER Standard also encompasses discretion on the part of the functional entities to “identif[y]”8 which personnel fall within the definition of Operations Support Personnel and therefore require
training pursuant to the PER Standard; this is reasonable and recognizes that functional entities are in the best position to make that identification.  In its order, the Commission should confirm that functional entities have the discretion to make that identification.

Third, the proposed standard (in Requirement R3) requires each relevant functional entity
to verify at least initially the capabilities of its personnel.  This requirement reasonably verifies
the performance capabilities of personnel to perform company-specific real-time reliability-
related tasks.  It provides a level of assurance that each entity is adequately staffed to perform its
relevant real-time functions.  Risks related to human performance can never be fully mitigated,
but verification provides a modicum of assurance that personnel are qualified for their positions.
With respect to the frequency of verification under the standard, setting the floor at a one-time
verification is appropriate.  Entities then have discretion to apply verification processes more
frequently based on their particular needs, which may vary based on several factors - e.g., the
functions they perform, their training programs, work schedules, and years of experience of
relevant personnel.  The relevant requirement also requires re-verification within six months
anytime there is a new or modified real-time reliability-related task.  Re-verification under these
circumstances is reasonable.

Fourth, the proposed standard requires specific training requirements for RC, BA, TOP and TO personnel that are involved with the operation of facilities that either have an

 

 

 

 

8 See proposed Reliability Standard PER-005-2, Requirement R5.

 

 

5


 

 

 

 

 

Interconnection Reliability Operating Limit (“IROL”), or are used to mitigate an IROL.9  In

particular, the proposed standard requires some type of simulation-based training.  Providing a
general obligation of simulation-based training reasonably leaves the specific type of simulation
training to the functional entity, is appropriate.  The relevant functional entities are in the best
position to understand their functions and related processes and procedures used to execute those
functions, and, accordingly, are in the best position to develop the most effective simulation
training for personnel involved in operational actions that could impact an IROL.
Finally, the ISO/RTO Commenters support NERC’s conclusion that personnel who
support Energy Management Systems (“EMS”) applications should not be included at this time
in the training requirements enunciated in the PER Standard.  By way of background, the
Commission approved Reliability Standards PER-005-1 and PER-004-2 in Order No. 742,10 but
NERC had yet to consider “whether personnel who support EMS applications should be included
in mandatory training requirements.”11    As indicated in the Petition, the NERC standard
drafting team “determined, based on research conducted by the NERC Operating Committee’s
Event Analysis Subcommittee, that there was insufficient evidence at this time to warrant an
extension of the mandatory training requirements to personnel that support EMS applications,”
but NERC would “continue to assess the need for mandatory training of these personnel.”12
As explained by NERC, “the Event Analysis Subcommittee reviewed the reportable
events in NERC’s Event Analysis database to determine whether there was any evidence
demonstrating a need to include EMS support personnel in NERC’s mandatory training

 

9 See proposed Reliability Standard PER-005-2, Requirement R4.

10 Petition at 11, citing System Personnel Training Reliability Standards, Order No. 742, 133 FERC ¶ 61,159 at P 1 (2010) (“Order No. 742”).

11 Petition at 11.

12 Petition at 19.

 

 

6


 

 

Reliability Standard.”13  In particular, the Subcommittee queried the Event Analysis database of
208 cause-coded reportable events for those cause codes that pertained to human error or lack of
training.  Of the 10 events to which human error or lack of training was a contributing factor, six
were related to loss of EMS or Supervisory Control and Data Acquisition (“SCADA”)
applications.  Out of those six events, only two were deemed to be due to a lack of training.14
For this reason, the Event Analysis Subcommittee concluded that with respect to EMS support
personnel, “the evidence does not support a need for such personnel to be trained under
Reliability Standard PER-005.”15  As indicated, NERC relied on this research in the draft of the
PER Standard.  The ISO/RTO Commenters support this conclusion, which is consistent with its
members’ own experience.

For the above reasons, the ISO/RTO Commenters believe the PER Standard is reasonable with respect to its goal of supporting real-time system operations and reliability.  Accordingly, the Commission should approve the standard as filed by NERC.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13 Petition at 31.

14 Petition at 31-32.

15 Petition at 32.

 

 

7


 

 

 

 

 

IV.CONCLUSION

The ISO/RTO Commenters respectfully request that the Commission approve the PER

Standard as filed.

Respectfully submitted,


 

/s/ Anna McKenna

Roger E. Collanton
General Counsel
Anna A. McKenna

Assistant General Counsel-Regulatory

California Independent System Operator Corporation

250 Outcropping Way
Folsom, California 95630

 

/s/ Jessica Savage

Jessica Savage

Manager, Government and Regulatory Affairs

Independent Electricity System Operator

Station A, Box 4474

Toronto, Ontario  M5W 4E5

 

 

 

 

 

 

/s/ Stephen G. Kozey

Stephen G. Kozey

Senior Vice President, Legal and Compliance Services, General Counsel and Secretary

Midcontinent Independent System Operator, Inc.

P.O. Box 4202
Carmel, Indiana 46082-4202


/s/ Matthew Morais

Matthew Morais

Director, Federal Policy

Electric Reliability Council of Texas, Inc.

2705 West Lake Drive
Taylor, Texas 76574

 

 

 

 

/s/ Theodore J. Paradise

Raymond W. Hepper
Vice President, General
Counsel, and Secretary
Theodore J. Paradise

Assistant General Counsel - Operations and Planning

Margoth R. Caley
Regulatory Counsel

ISO New England Inc.

One Sullivan Road

Holyoke, MA 01040-2841

 

/s/ Carl F. Patka

Carl F. Patka

Assistant General Counsel Christopher Sharp

Compliance Attorney Raymond Stalter

Director, Regulatory Affairs

New York Independent System Operator,
Inc.

10 Krey Blvd.

Rensselaer, New York 12144

 

 

 

 

 

 

8


 

 

 

 

 

/s/ Paul Suskie

Paul Suskie

Executive Vice President, Regulatory Policy and General Counsel

Southwest Power Pool, Inc.

201 Worthen Drive

Little Rock, AR 72223

 

 

 

 

Dated:    April 11, 2014

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 